Vulnerabilities > Schneider Electric > Modicon M340 Bmxp342030 Firmware

DATE CVE VULNERABILITY TITLE RISK
2023-02-01 CVE-2021-22786 Information Exposure vulnerability in Schneider-Electric products
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol.
network
low complexity
schneider-electric CWE-200
7.5
2023-01-31 CVE-2022-45789 Authentication Bypass by Capture-replay vulnerability in Schneider-Electric products
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session.
network
low complexity
schneider-electric CWE-294
critical
9.8
2023-01-30 CVE-2022-45788 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller.
network
low complexity
schneider-electric CWE-754
critical
9.8
2022-11-22 CVE-2022-0222 Improper Privilege Management vulnerability in Schneider-Electric products
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP.
network
low complexity
schneider-electric CWE-269
7.5
2022-02-04 CVE-2022-22724 Resource Exhaustion vulnerability in Schneider-Electric products
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC.
network
low complexity
schneider-electric CWE-400
5.0
2021-07-14 CVE-2021-22779 Authentication Bypass by Spoofing vulnerability in Schneider-Electric products
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
network
low complexity
schneider-electric CWE-290
6.4
2019-03-21 CVE-2015-6462 Cross-site Scripting vulnerability in Schneider-Electric products
Reflected Cross-Site Scripting (nonpersistent) allows an attacker to craft a specific URL, which contains Java script that will be executed on the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC client browser.
network
low complexity
schneider-electric CWE-79
5.4
2019-03-21 CVE-2015-6461 Improper Input Validation vulnerability in Schneider-Electric products
Remote file inclusion allows an attacker to craft a specific URL referencing the Schneider Electric Modicon BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, or BMXP342030H PLC web server, which, when launched, will result in the browser redirecting to a remote file via a Java script loaded with the web page.
network
low complexity
schneider-electric CWE-20
5.4
2017-06-30 CVE-2017-6017 Resource Exhaustion vulnerability in Schneider-Electric products
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H.
network
low complexity
schneider-electric CWE-400
7.5
2014-10-03 CVE-2014-0754 Path Traversal vulnerability in Schneider-Electric products
Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec before 5.5, 140NOC78x Exec before 1.62, 140NOE77x Exec before 6.2, BMXNOC0401 before 2.05, BMXNOE0100 before 2.9, BMXNOE0110x Exec before 6.0, TSXETC101 Exec before 2.04, TSXETY4103x Exec before 5.7, TSXETY5103x Exec before 5.9, TSXP57x ETYPort Exec before 5.7, and TSXP57x Ethernet Copro Exec before 5.5 allows remote attackers to visit arbitrary resources via a crafted HTTP request.
network
low complexity
schneider-electric CWE-22
critical
10.0