Vulnerabilities > Schneider Electric > Bmxnoe0110 Firmware > High

DATE CVE VULNERABILITY TITLE RISK
2022-02-11 CVE-2021-22785 Information Exposure vulnerability in Schneider-Electric products
A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device.
network
low complexity
schneider-electric CWE-200
7.5
2022-02-11 CVE-2021-22787 Improper Input Validation vulnerability in Schneider-Electric products
A CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request to the web server of the device.
network
low complexity
schneider-electric CWE-20
7.5
2022-02-11 CVE-2021-22788 Out-of-bounds Write vulnerability in Schneider-Electric products
A CWE-787: Out-of-bounds Write vulnerability exists that could cause denial of service when an attacker sends a specially crafted HTTP request to the web server of the device.
network
low complexity
schneider-electric CWE-787
7.5
2020-12-11 CVE-2020-7539 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7536 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7535 Path Traversal vulnerability in Schneider-Electric products
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
network
low complexity
schneider-electric CWE-22
7.5
2017-06-30 CVE-2017-6017 Resource Exhaustion vulnerability in Schneider-Electric products
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H.
network
low complexity
schneider-electric CWE-400
7.5