Vulnerabilities > Rockwellautomation > Factorytalk Services Platform

DATE CVE VULNERABILITY TITLE RISK
2024-01-31 CVE-2024-21917 Improper Verification of Cryptographic Signature vulnerability in Rockwellautomation Factorytalk Services Platform
A vulnerability exists in Rockwell Automation FactoryTalk® Service Platform that allows a malicious user to obtain the service token and use it for authentication on another FTSP directory.
network
low complexity
rockwellautomation CWE-347
critical
9.1
2023-10-27 CVE-2023-46290 Improper Authentication vulnerability in Rockwellautomation Factorytalk Services Platform
Due to inadequate code logic, a previously unauthenticated threat actor could potentially obtain a local Windows OS user token through the FactoryTalk® Services Platform web service and then use the token to log in into FactoryTalk® Services Platform .
network
high complexity
rockwellautomation CWE-287
8.1
2022-04-01 CVE-2021-32960 Incorrect Authorization vulnerability in Rockwellautomation Factorytalk Services Platform
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name.
6.0
2022-02-24 CVE-2020-14478 XXE vulnerability in Rockwellautomation Factorytalk Services Platform
A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content.
local
low complexity
rockwellautomation CWE-611
5.6
2021-03-18 CVE-2020-14516 Use of Password Hash With Insufficient Computational Effort vulnerability in Rockwellautomation Factorytalk Services Platform 6.10.00/6.11.00
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.
network
low complexity
rockwellautomation CWE-916
7.5
2021-03-03 CVE-2021-22681 Insufficiently Protected Credentials vulnerability in Rockwellautomation products
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
network
low complexity
rockwellautomation CWE-522
7.5
2020-06-23 CVE-2020-12033 Improper Input Validation vulnerability in Rockwellautomation Factorytalk Services Platform
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
low complexity
rockwellautomation CWE-20
5.8
2020-03-23 CVE-2020-6967 Deserialization of Untrusted Data vulnerability in Rockwellautomation Factorytalk Services Platform
In Rockwell Automation all versions of FactoryTalk Diagnostics software, a subsystem of the FactoryTalk Services Platform, FactoryTalk Diagnostics exposes a .NET Remoting endpoint via RNADiagnosticsSrv.exe at TCPtcp/8082, which can insecurely deserialize untrusted data.
network
low complexity
rockwellautomation CWE-502
critical
10.0
2019-01-24 CVE-2018-18981 Out-of-bounds Write vulnerability in Rockwellautomation Factorytalk Services Platform
In Rockwell Automation FactoryTalk Services Platform 2.90 and earlier, a remote unauthenticated attacker could send numerous crafted packets to service ports resulting in memory consumption that could lead to a partial or complete denial-of-service condition to the affected services.
network
low complexity
rockwellautomation CWE-787
7.8
2015-03-31 CVE-2014-9209 Unspecified vulnerability in Rockwellautomation products
Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.
6.9