Vulnerabilities > Hitachienergy > Relion 650 Firmware
DATE | CVE | VULNERABILITY TITLE | RISK |
---|---|---|---|
2024-01-04 | CVE-2022-3864 | Improper Verification of Cryptographic Signature vulnerability in Hitachienergy products A vulnerability exists in the Relion update package signature validation. | 4.5 |
2023-12-01 | CVE-2023-4518 | Improper Validation of Specified Quantity in Input vulnerability in Hitachienergy products A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. | 7.5 |
2023-02-21 | CVE-2022-3353 | Improper Resource Shutdown or Release vulnerability in Hitachienergy products A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections. Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.5.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.8.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.0.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.5:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:mms:2.2.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.2:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:7:*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:8:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:1.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.0.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:1.3.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.1.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.1:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relionSAM600-IO:2.2.5:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion650:2.2.*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:rtu500cmu:12.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:rtu500cmu:13.*.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:2.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_4:3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:txpert_hub_coretec_5:3.0:*:*:*:*:*:*:* | 7.5 |
2021-11-18 | CVE-2021-35534 | Improper Privilege Management vulnerability in Hitachienergy products Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. | 7.2 |
2021-11-18 | CVE-2021-35535 | Insecure Default Initialization of Resource vulnerability in Hitachienergy products Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. | 8.1 |
2021-06-14 | CVE-2021-27196 | Improper Input Validation vulnerability in Hitachienergy products Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. | 7.5 |
2019-11-27 | CVE-2019-18247 | Improper Input Validation vulnerability in Hitachienergy Relion 650 Firmware and Relion 670 Firmware An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service. | 7.5 |