2017-06-30 | CVE-2017-7905 | Use of Insufficiently Random Values vulnerability in GE products A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. | 5.0 |
2017-02-13 | CVE-2016-9360 | Insufficiently Protected Credentials vulnerability in GE Cimplicity An issue was discovered in General Electric (GE) Proficy HMI/SCADA iFIX Version 5.8 SIM 13 and prior versions, Proficy HMI/SCADA CIMPLICITY Version 9.0 and prior versions, and Proficy Historian Version 6.0 and prior versions. | 4.4 |
2016-07-15 | CVE-2016-5787 | Exposure of Resource to Wrong Sphere vulnerability in GE Cimplicity General Electric (GE) Digital Proficy HMI/SCADA - CIMPLICITY before 8.2 SIM 27 mishandles service DACLs, which allows local users to modify a service configuration via unspecified vectors. | 4.6 |
2016-02-05 | CVE-2016-0862 | Information Exposure vulnerability in GE Snmp/Web Adapter Firmware 4.7 General Electric (GE) Industrial Solutions UPS SNMP/Web Adapter devices with firmware before 4.8 allow remote authenticated users to obtain sensitive cleartext account information via unspecified vectors. | 4.0 |
2015-03-14 | CVE-2014-5409 | Predictable Random Number Generator Weakness in General Electric (GE) Hydran M2 The 17046 Ethernet card before 94450214LFMT100SEM-L.R3-CL for the GE Digital Energy Hydran M2 does not properly generate random values for TCP Initial Sequence Numbers (ISNs), which makes it easier for remote attackers to spoof packets by predicting these values. | 5.0 |
2015-02-07 | CVE-2014-9203 | Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in multiple products Buffer overflow in the Field Device Tool (FDT) Frame application in the HART Device Type Manager (DTM) library, as used in MACTek Bullet DTM 1.00.0, GE Vector DTM 1.00.0, GE SVi1000 Positioner DTM 1.00.0, GE SVI II AP Positioner DTM 2.00.1, and GE 12400 Level Transmitter DTM 1.00.0, allows remote attackers to cause a denial of service (DTM outage) via crafted packets. | 5.0 |
2015-01-17 | CVE-2014-5419 | Cryptographic Issues vulnerability in GE products GE Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware 4.2.1 and earlier and Multilink ML810, ML3000, and ML3100 switches with firmware 5.2.0 and earlier use the same RSA private key across different customers' installations, which makes it easier for remote attackers to obtain the cleartext content of network traffic by reading this key from a firmware image and then sniffing the network. | 5.0 |
2015-01-17 | CVE-2014-2355 | Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in GE Intelligent Platforms Proficy Hmi/Scada Cimplicity The (1) CimView and (2) CimEdit components in GE Proficy HMI/SCADA-CIMPLICITY 8.2 and earlier allow remote attackers to gain privileges via a crafted CIMPLICITY screen (aka .CIM) file. | 6.9 |
2013-11-22 | CVE-2013-2823 | Improper Input Validation vulnerability in multiple products The (1) Catapult DNP3 I/O driver before 7.2.0.60 and the (2) GE Intelligent Platforms Proficy DNP3 I/O driver before 7.20k, as used in DNPDrv.exe (aka the DNP master station server) in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY and iFIX, allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line. | 4.7 |
2013-01-27 | CVE-2013-0653 | Path Traversal vulnerability in GE products Directory traversal vulnerability in substitute.bcl in the WebView CimWeb subsystem in GE Intelligent Platforms Proficy HMI/SCADA - CIMPLICITY 4.01 through 8.0, and Proficy Process Systems with CIMPLICITY, allows remote attackers to read arbitrary files via a crafted packet. | 4.3 |