2019-12-18 CVE-2019-18995 Improper Input Validation vulnerability in ABB Pb610 Panel Builder 600 1.90.0.975/2.8.0.424
The HMISimulator component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier fails to validate the content-length field for HTTP requests, exposing HMISimulator to denial of service via crafted HTTP requests manipulating the content-length setting.
network
low complexity
abb CWE-20
5.3
2019-12-18 CVE-2019-18994 Improper Input Validation vulnerability in ABB Pb610 Panel Builder 600 1.90.0.975/2.8.0.424
Due to a lack of file length check, the HMIStudio component of ABB PB610 Panel Builder 600 versions 2.8.0.424 and earlier crashes when trying to load an empty *.JPR application file.
network
low complexity
abb CWE-20
6.5
2019-11-26 CVE-2019-18250 Improper Authentication vulnerability in ABB products
In all versions of ABB Power Generation Information Manager (PGIM) and Plant Connect, the affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from the affected device.
network
low complexity
abb CWE-287
critical
9.8
2019-06-27 CVE-2019-7225 Use of Hard-coded Credentials vulnerability in ABB products
The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface.
low complexity
abb CWE-798
8.8
2019-06-27 CVE-2019-7227 Path Traversal vulnerability in ABB Pb610 Panel Builder 600 Firmware 1.91/2.8.0.367
In the ABB IDAL FTP server, an authenticated attacker can traverse to arbitrary directories on the hard disk with "CWD ../" and then use the FTP server functionality to download and upload files.
low complexity
abb CWE-22
7.3
2019-06-27 CVE-2019-7226 Improper Authentication vulnerability in ABB Pb610 Panel Builder 600 Firmware 1.91/2.8.0.367
The ABB IDAL HTTP server CGI interface contains a URL that allows an unauthenticated attacker to bypass authentication and gain access to privileged functions.
low complexity
abb CWE-287
8.8
2019-06-27 CVE-2019-7228 Use of Externally-Controlled Format String vulnerability in ABB Pb610 Panel Builder 600 Firmware 1.91/2.8.0.367
The ABB IDAL HTTP server mishandles format strings in a username or cookie during the authentication process.
low complexity
abb CWE-134
8.8
2019-06-24 CVE-2019-7231 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in ABB Pb610 Panel Builder 600 Firmware 1.91/2.8.0.367
The ABB IDAL FTP server is vulnerable to a buffer overflow when a long string is sent by an authenticated attacker.
low complexity
abb CWE-119
5.7
2019-06-24 CVE-2019-7229 Download of Code Without Integrity Check vulnerability in ABB products
The ABB CP635 HMI uses two different transmission methods to upgrade its firmware and its software components: "Utilization of USB/SD Card to flash the device" and "Remote provisioning process via ABB Panel Builder 600 over FTP." Neither of these transmission methods implements any form of encryption or authenticity checks against the new firmware HMI software binary files.
high complexity
abb CWE-494
8.3
2019-06-24 CVE-2019-7232 Out-of-bounds Write vulnerability in ABB Pb610 Panel Builder 600 Firmware 1.91/2.8.0.367
The ABB IDAL HTTP server is vulnerable to a buffer overflow when a long Host header is sent in a web request.
low complexity
abb CWE-787
8.8