Vulnerabilities > Siemens > Simatic Step 7 > 5.5

DATE CVE VULNERABILITY TITLE RISK
2015-04-06 CVE-2015-1602 Information Exposure vulnerability in Siemens Simatic Step 7 12.0/13.0/5.5
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 improperly stores password data within project files, which makes it easier for local users to determine cleartext (1) protection-level passwords or (2) web-server passwords by leveraging the ability to read these files.
local
low complexity
siemens CWE-200
2.1
2015-04-06 CVE-2015-1601 7PK - Security Features vulnerability in Siemens Simatic Step 7 12/13/5.5
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 allows man-in-the-middle attackers to obtain sensitive information or modify transmitted data via unspecified vectors.
network
siemens CWE-254
6.8
2015-03-07 CVE-2015-1594 Unspecified vulnerability in Siemens products
Untrusted search path vulnerability in Siemens SIMATIC ProSave before 13 SP1; SIMATIC CFC before 8.0 SP4 Upd9 and 8.1 before Upd1; SIMATIC STEP 7 before 5.5 SP1 HF2, 5.5 SP2 before HF7, 5.5 SP3, and 5.5 SP4 before HF4; SIMOTION Scout before 4.4; and STARTER before 4.4 HF3 allows local users to gain privileges via a Trojan horse application file.
local
siemens
6.9
2015-02-18 CVE-2015-1356 Permissions, Privileges, and Access Controls vulnerability in Siemens Simatic Step 7 12.0/13.0/5.5
Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 determines a user's privileges on the basis of project-file fields that lack integrity protection, which allows remote attackers to establish arbitrary authorization data via a modified file.
4.4
2015-02-18 CVE-2015-1355 Cryptographic Issues vulnerability in Siemens Simatic Step 7 12.0/13.0/5.5
Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 uses a weak password-hash algorithm, which makes it easier for local users to determine cleartext passwords by reading a project file and conducting a brute-force attack.
local
low complexity
siemens CWE-310
2.1
2012-07-26 CVE-2012-3015 Unspecified vulnerability in Siemens Simatic Pcs7 and Simatic Step 7
Untrusted search path vulnerability in Siemens SIMATIC STEP7 before 5.5 SP1, as used in SIMATIC PCS7 7.1 SP3 and earlier and other products, allows local users to gain privileges via a Trojan horse DLL in a STEP7 project folder.
local
siemens
6.9