DATE CVE VULNERABILITY TITLE RISK
2020-12-11 CVE-2020-7536 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7535 Path Traversal vulnerability in Schneider-Electric products
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
network
low complexity
schneider-electric CWE-22
7.5
2020-01-06 CVE-2019-6855 Incorrect Authorization vulnerability in Schneider-Electric products
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
network
low complexity
schneider-electric CWE-863
7.5
2018-04-18 CVE-2018-7762 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric products
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
network
low complexity
schneider-electric CWE-119
7.5
2018-04-18 CVE-2018-7759 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric products
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200.
network
low complexity
schneider-electric CWE-119
7.5
2017-06-30 CVE-2017-6017 Resource Exhaustion vulnerability in Schneider-Electric products
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H.
network
low complexity
schneider-electric CWE-400