Vulnerabilities > Schneider Electric > Modicon M340 Bmxp3420102Cl Firmware

DATE CVE VULNERABILITY TITLE RISK
2020-12-11 CVE-2020-7549 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP.
network
low complexity
schneider-electric CWE-754
5.3
2020-12-11 CVE-2020-7543 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7542 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7541 Forced Browsing vulnerability in Schneider-Electric products
A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP.
network
low complexity
schneider-electric CWE-425
5.3
2020-12-11 CVE-2020-7540 Missing Authentication for Critical Function vulnerability in Schneider-Electric products
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.
network
low complexity
schneider-electric CWE-306
critical
9.8
2020-12-11 CVE-2020-7539 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7537 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7536 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
network
low complexity
schneider-electric CWE-754
7.5
2020-12-11 CVE-2020-7535 Path Traversal vulnerability in Schneider-Electric products
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
network
low complexity
schneider-electric CWE-22
7.5
2018-04-18 CVE-2018-7762 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric products
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
network
low complexity
schneider-electric CWE-119
7.5