Vulnerabilities > Schneider Electric > Modicon M340 Bmxp342010 Firmware > Medium

DATE CVE VULNERABILITY TITLE RISK
2022-02-04 CVE-2022-22724 Resource Exhaustion vulnerability in Schneider-Electric products
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC.
network
low complexity
schneider-electric CWE-400
5.0
2021-07-14 CVE-2021-22779 Authentication Bypass by Spoofing vulnerability in Schneider-Electric products
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
network
low complexity
schneider-electric CWE-290
6.4