Vulnerabilities > Schneider Electric > Interactive Graphical Scada System > Critical

DATE CVE VULNERABILITY TITLE RISK
2021-03-11 CVE-2021-22709 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Interactive Graphical Scada System
A CWE-119:Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Interactive Graphical SCADA System (IGSS) Definition (Def.exe) V15.0.0.21041 and prior, which could result in loss of data or remote code execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition.
network
schneider-electric CWE-119
critical
9.3
2021-03-11 CVE-2021-22710 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Interactive Graphical Scada System
A CWE-119:Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Interactive Graphical SCADA System (IGSS) Definition (Def.exe) V15.0.0.21041 and prior, which could cause remote code execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition.
network
schneider-electric CWE-119
critical
9.3
2021-03-11 CVE-2021-22711 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Interactive Graphical Scada System
A CWE-119:Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Interactive Graphical SCADA System (IGSS) Definition (Def.exe) V15.0.0.21041 and prior, which could result in arbitrary read or write conditions when malicious CGF (Configuration Group File) file is imported to IGSS Definition due to missing validation of input data.
network
schneider-electric CWE-119
critical
9.3
2021-03-11 CVE-2021-22712 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Interactive Graphical Scada System
A CWE-119:Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Interactive Graphical SCADA System (IGSS) Definition (Def.exe) V15.0.0.21041 and prior, which could result in arbitrary read or write conditions when malicious CGF (Configuration Group File) file is imported to IGSS Definition due to an unchecked pointer address.
network
schneider-electric CWE-119
critical
9.3
2013-01-21 CVE-2013-0657 Buffer Errors vulnerability in Schneider-Electric Interactive Graphical Scada System 10.0/9.0
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol.
network
low complexity
schneider-electric CWE-119
critical
10.0