Vulnerabilities > Schneider Electric > Ecostruxure Process Expert

DATE CVE VULNERABILITY TITLE RISK
2024-02-14 CVE-2023-27975 Unspecified vulnerability in Schneider-Electric products
CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation.
local
low complexity
schneider-electric
7.1
2024-02-14 CVE-2023-6409 Unspecified vulnerability in Schneider-Electric products
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert.
local
low complexity
schneider-electric
7.7
2023-01-31 CVE-2022-45789 Unspecified vulnerability in Schneider-Electric products
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session.
network
low complexity
schneider-electric
critical
9.8
2023-01-30 CVE-2022-45788 Unspecified vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller.
network
low complexity
schneider-electric
critical
9.8
2022-09-12 CVE-2022-37300 Unspecified vulnerability in Schneider-Electric products
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus.
network
low complexity
schneider-electric
critical
9.8
2022-04-14 CVE-2022-26507 Out-of-bounds Write vulnerability in multiple products
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7.
network
low complexity
att schneider-electric CWE-787
critical
9.8
2022-04-13 CVE-2021-22797 Unspecified vulnerability in Schneider-Electric products
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal) vulnerability exists that could cause malicious script to be deployed in an unauthorized location and may result in code execution on the engineering workstation when a malicious project file is loaded in the engineering software.
local
low complexity
schneider-electric
7.8
2022-03-09 CVE-2022-24323 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data.
network
high complexity
schneider-electric CWE-754
5.9
2021-07-14 CVE-2021-22778 Unspecified vulnerability in Schneider-Electric products
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file.
local
low complexity
schneider-electric
7.1
2021-07-14 CVE-2021-22779 Unspecified vulnerability in Schneider-Electric products
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
network
low complexity
schneider-electric
critical
9.1