Vulnerabilities > Schneider Electric > Ecostruxure GEO Scada Expert 2019

DATE CVE VULNERABILITY TITLE RISK
2023-02-24 CVE-2023-0595 Improper Encoding or Escaping of Output vulnerability in Schneider-Electric products
A CWE-117: Improper Output Neutralization for Logs vulnerability exists that could cause the misinterpretation of log files when malicious packets are sent to the Geo SCADA server's database web port (default 443).
network
low complexity
schneider-electric CWE-116
5.3
2023-01-31 CVE-2023-22610 Incorrect Authorization vulnerability in Schneider-Electric products
A CWE-863: Incorrect Authorization vulnerability exists that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port.
network
low complexity
schneider-electric CWE-863
7.5
2023-01-31 CVE-2023-22611 Unspecified vulnerability in Schneider-Electric products
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause information disclosure when specific messages are sent to the server over the database server TCP port.
network
low complexity
schneider-electric
7.5
2022-02-09 CVE-2022-24318 Inadequate Encryption Strength vulnerability in Schneider-Electric products
A CWE-326: Inadequate Encryption Strength vulnerability exists that could cause non-encrypted communication with the server when outdated versions of the ViewX client are used.
network
low complexity
schneider-electric CWE-326
5.0
2022-02-09 CVE-2022-24319 Improper Certificate Validation vulnerability in Schneider-Electric products
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA web server are intercepted.
4.3
2022-02-09 CVE-2022-24320 Improper Certificate Validation vulnerability in Schneider-Electric products
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA database server are intercepted.
4.3
2022-02-09 CVE-2022-24321 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause Denial of Service against the Geo SCADA server when receiving a malformed HTTP request.
network
low complexity
schneider-electric CWE-754
5.0
2021-05-26 CVE-2021-22741 Use of Password Hash With Insufficient Computational Effort vulnerability in Schneider-Electric products
Use of Password Hash with Insufficient Computational Effort vulnerability exists in ClearSCADA (all versions), EcoStruxure Geo SCADA Expert 2019 (all versions), and EcoStruxure Geo SCADA Expert 2020 (V83.7742.1 and prior), which could cause the revealing of account credentials when server database files are available.
local
low complexity
schneider-electric CWE-916
4.6
2020-12-11 CVE-2020-28219 Insufficiently Protected Credentials vulnerability in Schneider-Electric products
A CWE-522: Insufficiently Protected Credentials vulnerability exists in EcoStruxure Geo SCADA Expert 2019 (Original release and Monthly Updates to September 2020, from 81.7268.1 to 81.7578.1) and EcoStruxure Geo SCADA Expert 2020 (Original release and Monthly Updates to September 2020, from 83.7551.1 to 83.7578.1), that could cause exposure of credentials to server-side users when web users are logged in to Virtual ViewX.
local
low complexity
schneider-electric CWE-522
2.1