Vulnerabilities > Schneider Electric > Ecostruxure Control Expert > 15.0
DATE | CVE | VULNERABILITY TITLE | RISK |
---|---|---|---|
2024-02-14 | CVE-2023-27975 | Unspecified vulnerability in Schneider-Electric products CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation. | 7.1 |
2024-02-14 | CVE-2023-6408 | Unspecified vulnerability in Schneider-Electric products CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack. | 8.1 |
2024-02-14 | CVE-2023-6409 | Unspecified vulnerability in Schneider-Electric products CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert. | 7.7 |
2022-03-09 | CVE-2022-24322 | Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Ecostruxure Control Expert 14.0/14.1/15.0 A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data. | 5.9 |
2022-03-09 | CVE-2022-24323 | Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. | 5.9 |
2021-07-14 | CVE-2021-22778 | Unspecified vulnerability in Schneider-Electric products Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file. | 7.1 |
2021-07-14 | CVE-2021-22779 | Unspecified vulnerability in Schneider-Electric products Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | 9.1 |
2021-07-14 | CVE-2021-22780 | Unspecified vulnerability in Schneider-Electric products Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. | 7.1 |
2021-07-14 | CVE-2021-22781 | Insufficiently Protected Credentials vulnerability in Schneider-Electric products Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file. | 5.5 |
2021-07-14 | CVE-2021-22782 | Unspecified vulnerability in Schneider-Electric products Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file. | 5.5 |