DATE CVE VULNERABILITY TITLE RISK
2024-02-14 CVE-2023-27975 Unspecified vulnerability in Schneider-Electric products
CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation.
local
low complexity
schneider-electric
7.1
2024-02-14 CVE-2023-6408 Unspecified vulnerability in Schneider-Electric products
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.
network
high complexity
schneider-electric
8.1
2024-02-14 CVE-2023-6409 Unspecified vulnerability in Schneider-Electric products
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert.
local
low complexity
schneider-electric
7.7
2022-03-09 CVE-2022-24322 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability in Schneider-Electric Ecostruxure Control Expert 14.0/14.1/15.0
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data.
network
high complexity
schneider-electric CWE-119
5.9
2022-03-09 CVE-2022-24323 Improper Check for Unusual or Exceptional Conditions vulnerability in Schneider-Electric products
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data.
network
high complexity
schneider-electric CWE-754
5.9
2021-07-14 CVE-2021-22778 Unspecified vulnerability in Schneider-Electric products
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file.
local
low complexity
schneider-electric
7.1
2021-07-14 CVE-2021-22779 Unspecified vulnerability in Schneider-Electric products
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
network
low complexity
schneider-electric
critical
9.1
2021-07-14 CVE-2021-22780 Unspecified vulnerability in Schneider-Electric products
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources.
local
low complexity
schneider-electric
7.1
2021-07-14 CVE-2021-22781 Insufficiently Protected Credentials vulnerability in Schneider-Electric products
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file.
local
low complexity
schneider-electric CWE-522
5.5
2021-07-14 CVE-2021-22782 Unspecified vulnerability in Schneider-Electric products
Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file.
local
low complexity
schneider-electric
5.5