Vulnerabilities > CVE-2013-2805 - Out-of-bounds Read vulnerability in Rockwellautomation Rslinx Enterprise
Summary
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
Vulnerable Configurations
Common Weakness Enumeration (CWE)
Common Attack Pattern Enumeration and Classification (CAPEC)
- Overread Buffers An adversary attacks a target by providing input that causes an application to read beyond the boundary of a defined buffer. This typically occurs when a value influencing where to start or stop reading is set to reflect positions outside of the valid memory location of the buffer. This type of attack may result in exposure of sensitive information, a system crash, or arbitrary code execution.